  "demo": true,
  "site": "Northline Dallas Service",
  "project": "EV-service charger addition",
  "modeled_by": "Ampscale demo fixture",
  "existing_peak_kw": 312.2,
  "service": {
    "equipment": "MSB",
    "rating_amps": 800,
    "voltage": "480Y/277",
    "phase": "3 phase"
  },
  "proposed_loads": [
    {
      "name": "4 Level 2 service-bay chargers",
      "kw": 46,
      "status": "model_now"
    },
    {
      "name": "180 kW DC fast charger",
      "kw": 180,
      "status": "hold_for_review"
    }
  ],
  "guided_route": {
    "decision": "Add L2 now; route DCFC for review",
    "addable_kw_range": {
      "low": 74,
      "high": 96
    },
    "confidence_grade": 4,
    "next_owner": "electrician",
    "next_file": "confirm main-service label photo and current single-line"
  },
  "next_steps": [
    "Confirm service label photo is current",
    "Confirm EV-1 panel path and breaker space",
    "Decide whether DCFC is out of scope or staged for reviewer path"
  ],
  "boundary": "Modeled demo data only. Not a sealed calculation, permit approval, utility approval, or field verification."
}